NFM
200 Operation |
 |
|
The
FE-227™
clean
agent
gas
extinguishant
is
stored
commonly
in
welded
mild
steel
cylindrical
containers
which
are
designed
and
manufactured
to
BS
5045
Part
2
for
FE-227™
use
and
pressurized
with
dry
nitrogen
to
25
bars
at
20°C. |
FE-227™
automatic
fire
suppression
system
common
components
are
the
following: |
• Agent cylinder
• Release panel
• Discharge valve
• Detectors
• Actuator
• Manual release
• Discharge nozzle
• Sounder
• Piping network
• Flashers
|
FE-227™
extinguishes
a
fire
quickly
by
discharging
in
10
seconds
or
less.
The
agent
removes
heat
and
breaks
up
the
fire
at
molecular
level.
Common
operation
of
FE-227™
is
automatic.
However,
manual
release
also
can
be
done. |
|
|
1
-
A
fire
in
the
protected
area
is
sensed
by
strategically
located
detectors
and
a
signal
is
sent
to
the
control
unit. |
2
-
The
control
unit
performs
a
series
of
actions:
shutting
down
ventilation
systems
and
equipment,
sounding
alarms
and
starting
the
discharge
of
FE-227™
into
the
protected
area. |
3
-
The
FE-227™
agent
stored
in
agent
containers
is
propelled
through
piping
and
nozzles
into
the
protected
area. |
4
-
FE-227™
discharges
as
a
gas
to
all
areas
of
the
protected
area,
reaching
a
7%
concentration
in
ten
seconds
and
quickly
suppressing
the
fire.
No
fire,
no
mess,
back
in
business. |
|
|
|
|
|
|
|
| |
|
 |
 |
|
|
|
|
|
Copyright
2006-2007.
National Fire Fighting Manufacturing FZCO(NAFFCO), All
rights reserved
NAFFCO reserves the right to modify specifications without
prior notice.
Site powered by NAFFCO Creative Division. |
|
|