1. Ensure Automatic
ZONECHECK ic installed
both mechinically
and electrically,
commission and
texted prior to
leaving site.
2. If the Automatic
ZoneCheck could
be wired when
the sprikler system
zone is drained
down then it is
vitally important
that the ZoneCheck
red and green
valves are left
in the closed
position, to ensure
the motor is not
accidentally run
dry and damaged.
(Please ensure
the commisioning
engineer is aware
of the closed
Automatic ZoneCheck
valve status.)
3. Always use
a flat faced wrench
for Automatic
ZoneCheck Commissioning
4. The suggested
location for the
keyswitch is at
low level, adjacent
to fire alarm
panel.
5.Fix operating
instructions to
wall, preferablly
next to KeySwitch.
6. Each Automatic
ZoneCheck is factory
assembled and
tested.
DO NOT
attempt to reconfigure
tempering will
INVALIDATE
THE WARRANTY.
7. Standard Automatic
ZoneChecks are
"Right Handed".
"Left Handed"
ZoneChecks are
available on request.
8. Maximum working
pressure 12 bar,
test pressure
18 bar.
9.Use Automatic
ZoneCheck flow
switch testers
in wet-pipe system
only. DO
NOT use
in dry pipe, Delgue,
or preaction systems.
10. Only active
the Automatic
ZoneCheck KeySwitch
when the valves
are opened and
the sprinkler
system is full.
11. Three year
limited warranty
against defect
in material &
workmanship under
normal use and
service from the
date of manufacturing.
We are not obligated
to repair or replace
units which are
found to be defective
because of damage,
unreasonable use,
modifications,
or alterations
occuring after
the date of manufacturing.
In no case we
are liable for
any consequential
or incidental
demages for breach
of this or any
other warranty,
expresses or implied
whatsoever, even
if the loss or
damage is cause
by the company's
negligence or
fault.
|
| ----------------------------------------------------------------------------------------------------------- |
» Automatic ZoneCheck
Commissioning Procedure
»
Automatic ZoneCheck KeySwicth
Specification
»
Automatic ZoneCheck Wiring
|
|
| ----------------------------------------------------------------------------------------------------------- |
|
|
|
|
 |
 |
|
|
|
|
|