TR-FFT

Fire Fighters Telephone Control System

 

The TR-FFT is a Fire Fighters Telephone communication system. The TR-FFT Fire Fighter Telephone System provides supervision, annunciation, and control for local and remote telephone handsets. The TR-FFT with keypad, provides indications of phone activation, and corresponding trouble conditions. The TR-24Z-EXT expander board lets you add additional zones to the TR-FFT. The TR-FFT can use up to two additional TR-24Z-EXTs for a total of 72 zones. Each zone consists of one addressable monitor module (TR-Minimon) and a minimum of one Fire Fighter Telephone Jack (TR-FPJ).

 

INSTALLATION
The TR-FFT can be surface or flush mounted.

 

COMPATIBILITY
The TR-FFT is compatible with the following FACPs:
• TR-2100ECSR / TR-2100ECSB
• TR-2100R / TR-2100B
• TR-R2100R/ TR-R2100B

Contact Us to Purchase
Features

• TR-FFT Fire Fighter Telephone module for control and annunciation of up to 72 remote telephone jacks
• Fire Fighter Phone Jack (TR-FPJ) provides a plug-in location for the TR-RHS
• Single telephone station mount comes in a lockable cabinet containing one remote handset. Available in Recessed mount (TR-STSR) or surface mount (TR-STSS).
• Fire Fighter Handset Cabinet (TR-HSC) is used to store ten fire fighter handsets (TR-RHS)
• System Status LEDs
• Supports two FFT-24 zone expanders
• The TR-FFT supports up to 72 TR-Minimon devices on one FFT system
• Simplified installation by using single loop design
• JumpStart® auto-programming
• For retrofit projects, TR-FFT is compatible with any UL listed 24V regulated power supply

Specifications

PHYSICAL
Flush Mount Dimensions: 20¼”W x 26¾”H x 2.5”- 3”D (51.4 W x 68 H x 6.4-7.6 D cm)
Overall Dimensions: 20”W x 26½”H x 4.6”D
(50.75 W x 67.3 H x 11.8 D cm)
Weight: 53 lbs.
Color: Red

 

ENVIRONMENTAL
Operating Temperature: 32°F to 120°F (0°C to 49°C) Humidity: 10 to 93% relative humidity
(noncondensing)

 

ELECTRICAL
Voltage for the TR-FFT must be a power-limited, filtered, non resettable nominal 24 VDC source. The voltage source must be within the range of 17-29 VDC.
Active Current: 230 mA
Standby Current: 120 mA
SLC Circuit: 32V; 150mA
Audio Circuits: 17V; 53mA

 

ORDERING INFORMATION
TR-FFT: Fire Fighters Telephone
TR-Minimon: Mini monitor module
TR-ISO: Fault Isolator Module

 

ECS ACCESSORIES
TR-24Z-EXT: 24 Zone Expander
TR-FPJ: Remote Phone Jack
TR-RHS: Fire Fighters Remote Hand Set
TR-HSC: Fire Fighters Handset Cabinet. Holds up to 10 remote handsets
TR-STSR: Single Telephone Station Recessed. A lockable cabinet containing one remote handset. TR-STSS: Single Telephone Station Surface Mount. A lockable cabinet containing one remote handset.

 

AGENCY LISTINGS AND APPROVALS
UL Listed