Auto Align Beam Detector
Primary Input Power | 14 to 36 V DC |
---|---|
Standby Current (Depending On Number Of Detector Heads) |
Low Current : 5 mA to 8.5 mA @ 24 V DC High Current : 37 mA @ 24 V DC |
Alarm Current | 5 mA to 8.5 mA @ 24 V DC depending on number of detector heads used |
Relay Contacts | 1 A @ 30 V DC Resistive |
Reset Time | 5 seconds maximum |
Start Up Time | 45 seconds |
Optical Wavelength | 850 nm |
Temperature Rating UL Listed | 0°C to 38°C |
Primary Input Power | 14 to 36 V DC |
IP Rating | IP54 |
Dimension (W x H x L) & Weight | |
Head | 134 mm x 134 mm x 131 mm, 1470 g |
Controller | 202 mm x 87 mm x 230 mm, 1470 g |
Prism | 100 mm x 9.5 mm x 105 mm |
- Up to 2 Detector Heads report to One Ground Level Controller
- Built-in Laser-assisted prism mounting
- Auto-Alignment 2 to 4 minutes per head
- AutOptimise: Auto-Correction due to building shift
- Built-in electronic UL/ULC obscuration-acceptance fire test
- Contamination compensation
- Separate Trouble and Alarm relays for each of the 2 channels
- Password-protected settings
- Programmable alarm thresholds: 10% - 60% in 1% increments
- Programmable Fault and Alarm delay: 2-30 Seconds