End to End Beam Detector
Operating Range | 5 - 120 m |
---|---|
Operating Voltage Range | 12 to 36 VDC ±10% |
Operating Controller Current (with 1 or 2 Receivers) |
14 mA (constant) |
Operating Transmitter Current | 8 mA (per Transmitter) |
Power Down Reset Time | >20 seconds |
Fire and Fault Relay Contacts | Resistive VFCO 2A @ 30 VDC |
Operating Temp. (non-condensing) | -20°C to +55°C |
Optical Wavelength | 850 nm |
IP Rating | IP54 |
Relative Humidity (non-condensing) | 93% |
Dimension (W x H x L) & Weight | |
Control Unit | 203 mm x 124 mm x 71 mm, 600 g |
Transmitter & Receiver | 78 mm x 77 mm x 161 mm, 200 g |
- Separate Transmitter and Receiver Heads
- Range 5 m to 120 m, configurable per set of Detectors
- Lateral Spacing per NFPA 72 is 18 m
- Integral Laser Alignment in Receiver
- 2-wire Interface between Controller and Receiver
- Single and Twin Channel capability
- Separate Fire and Fault Relays per Detector
- Low Level Controller with LCD display
- Programmable Sensitivity and Fire Threshold
- Automatic Gain Control (AGC) for drift compensation
- Built-in electronic UL/ULC obscuration-acceptance fire test
- Knockouts for ease of installation and wiring
- Optional Transmitter powering from Controller