ML96 SERIES

ML96 panel is a modular 19” central battery system according to EN 50171 and BGV A3 featuring single-light monitoring without additional wiring, free programmable circuits and a 5-year log-book. The system is available in different cases with internal or external battery compartment.

The built-in Web interface with integrated visualization software makes it possible to display even large projects clearly on a building plan. In addition, the test results and incidents of a particular date are retrieved and displayed together with all relevant operating parameters. This minimizes the maintenance costs.

The system can be configured by keyboard, on the device itself or through a TCP / IP network connection to a remote PC. The 19” rack design allows to upgrade or exchange modules individually. The circuit module supplies all connected luminaires to the system with electricity. Each outlet can be programmed for circuit monitored systems and for single luminaire monitoring. A combined operation is also possible.

The combined case can hold up to 48 modules for up to 96 electrical circuits modules. Each module is designed for 2 output circuits, each with up to 20 lights. Each circuit can be programmed as continuous light, maintained light, switched maintained light or a staircase light. Maintained lights and emergency lights can be operated combined.

The ML96 panel allows the connection of LED lamps, fluorescent lamps or low-voltage halogen lamps. Up to 256 main stations and 32 substations per panel can be linked via a serial or TCP / IP connection to a network. This allows a maximum of a million lights to be connected and monitored to the whole system.

Contact Us to Purchase
Specifications
Case Material Steel-sheet RAL 7035
Dimensions (H x W x D) Various
Protection Category IP20 (Optional IP21*, IP54**)
Insulation Class I
Dimensions (H x W x D) MLW: 900 x 600 x 450 mm
(without battery cabinet)
MLX: 1850 x 800 x 600 mm                                                                                 MLS: 1800 x 600 x 450 mm                                                                               MLG: 1500 x 600 x 450 mm                                                                                MLK: 1000 x 600 x 450 mm
Cable Entry from top (900 mm cabinet from below also)
Voltage 3 x 230V AC 50/60Hz +/- 10%
Output Circuits Max. 96 circuits with switchover for non-maintained or maintained operation
Battery Maintenance-free, closed lead acid cell OGiV, OGi, OPzS or low-maintenance NiCd batteries
Output Voltage 230 V AC / 216V DC
Permissible Temperature 10 °C to 35 °C