We use cookies to make your experience better. To comply with the new e-Privacy directive, we need to ask for your consent to set the cookies. Learn more.
Industrial Warehouses
Smoke venting system using natural vents on the roof.
Makeup air for the natural vents.
| Minimum opening area of vents based on percentage of the area. | Maximum distance of vent from any part of the volume. |
| if 1% of the floor area | 18m |
| if 1.25% of the floor area | 21m |
| if 1.5% of the floor area | 24m |
- Smoke venting system using mechanical exhaust fans.
- Smoke exhaust fans for 6ach & makeup air by openings to the shutter door or louvers.
- Floor area exceeding 4000 m2 shall be provided with smoke curtains to accommodate a smoke reservoir.