Sounder Beacon Base
The Sounder Beacon Base is a loop-powered sounder and visual indicator combined with a standard Intelligent Mounting Base. It is used to signal a fire alarm in enclosed areas.
- Two volume ranges 55-75dB(A) and 75-91dB(A)
- Visual indicator flash rate of once per second
- Synchronisation of 'alert' and 'evacuate' tones
- Synchronisation of visual indicator flash
- Individual and group addressing
- Unique acoustic and visual indicator self-test
- Built-in Isolator (SEN-A4007)
Operating voltage | 17–28V DC (polarity sensitive) | |
---|---|---|
Protocol pulses | 5–9V | |
Current consumption at 24V | switch-on surge | <1.2mA |
quiescent | 300μA | |
sounder operated 55–75dB or 75–91dB |
8mA | |
Maximum sound output at 90° | 91dB(A) | |
Operating temperature | -20°C to 60°C | |
Humidity (no condensation) | 0–95% | |
IP rating | 21C | |
Dimensions (diameter x height) | 100 mm x 31.25 mm |