Three Channel Input/Output
The Three Channel Input/Output Unit provides three voltage-free, single pole, changeover relay outputs and three monitored switch inputs.
- Supervises one or more normally open switches on each of the three inputs
- Loop-powered
- Capable of switching up to 30V at 1A on each of the three outputs
Operating voltage | 17–28V DC | |
---|---|---|
Maximum current consumption at 28V DC no protocol |
LED Enabled | |
switch-on surge, max 150ms | 6.5mA | |
quiescent, 20kΩ EOL fitted | 3mA | |
Switch inputs closed | 6mA | |
LED Disabled | ||
switch-on surge, max 150ms | 6.5mA | |
quiescent, 20kΩ EOL fitted | 3mA | |
Switch inputs closed | 4mA | |
Maximum continuous current | 1A | |
Maximum switching current | 3A | |
On resistance | 0.2Ω | |
Switch input monitoring voltage (open-circuit condition) |
9–11V DC | |
Maximum cable resistance | 50Ω | |
Operating temperature | –20°C to +70°C | |
Humidity (no condensation) | 0–95% | |
IP rating | 54 | |
Dimensions (L x B x H) | 250 mm x 175 mm x 75 mm |