TR-CONTROL-6

The TR-CONTROL-6 is an addressable notification module for use with the Triga Series fire alarm control panels (FACPs). The TR-CONTROL-6 has six integrated modules for maximum flexibility, allowing you to add notification circuits wherever they are needed on an FACP signaling line circuit (SLC) loop.

 

The TR-CONTROL-6 provides supervised monitoring of wiring to load devices that require an external power supply or amplifier to operate, such as bells, horns, and strobes. It is capable of supporting Class B and Class A wiring.

 

Upon command from the FACP, the TR-CONTROL-6 will disconnect the supervision and connect the external power supply across the load device. The disconnection of the supervision provides a positive indication to the panel that the control relay actually turned on. The external power supply is always relay isolated from the SLC loop, so that a trouble condition on the power supply will never interfere with the rest of the system.

 

If needed, you can disable a maximum of three unused modules on the TR-CONTROL-6 board. Each module has terminals for connection to an external supply circuit for powering devices on its notification appliance circuit (NAC). One or more multiple power supplies can be used.

 

The TR-CONTROL-6 has a short circuit protection monitor for each module. The short circuit protection monitor protects external power supplies against short circuit conditions on the NAC. In addition, an algorithm is incorporated to find a short when the module is active. The module will close all circuits that are not shorted to find the NAC with the problem.

Contact Us to Purchase
Features

• Flexible solution for adding notification circuits where needed
• Removable 12 to 18 AWG plug-in terminal blocks
• Support for Class B or Class A wiring
• Individual LED for each module
• Two module mounting in the TR-IDP-ACB cabinet
• Unused modules can be disabled
• Rotary address switches for fast installation
• Mounting hardware included
• UL Listed

• FM approved

Specifications

PHYSICAL
Dimensions: 6.8″H x 5.8″W x 1.25″D
Shipping Weight: 6.3oz (196g)

 

ELECTRICAL RATINGS
Operating Voltage: 15 to 32VDC
Standby Current: 2.65mA @ 24V
Alarm Current: 35mA maximum (assumes all six relays have been switched once and all six LEDs solid on)
End-of-Line Resistance: 47kW
Maximum SLC Wiring Resistance: 41W Maximum NAC Wiring Resistance: 40W

 

ENVIRONMENTAL
Operating Temperature: 32º-120ºF (0ºC – 49ºC) Humidity: 10 to 85% non-condensing)

 

ORDERING INFORMATION
TR-CONTROL-6: Six Input notification module
ACCESSORIES
TR-IDP-ACB: Cabinet. 15.25″ H x 12.5″ W x 3″D

 

INSTALLATION
The TR-CONTROL-6 mounts in the Triga TR-IDP-ACB cabinet . The TR-IDP-ACB has a built-in chassis that will accommodate one or two TR-Control-6 modules.

 

COMPATIBILITY
The TR-CONTROL-6 is compatible with the following Triga Series FACPs:
• TR-2100R / ITR-2100B
• TR-2100ECSR / TR-2100ECSB
• TR-R2100R / TR-R2100B