TR-FFT

Fire Fighters Telephone Control System

 

The TR-FFT is a Fire Fighters Telephone communication system. The TR-FFT Fire Fighter Telephone System provides supervision, annunciation, and control for local and remote telephone handsets. The TR-FFT with keypad, provides indications of phone activation, and corresponding trouble conditions. The TR-24Z-EXT expander board lets you add additional zones to the TR-FFT. The TR-FFT can use up to two additional TR-24Z-EXTs for a total of 72 zones. Each zone consists of one addressable monitor module (TR-Minimon) and a minimum of one Fire Fighter Telephone Jack (TR-FPJ).

 

INSTALLATION
The TR-FFT can be surface or flush mounted.

 

COMPATIBILITY
The TR-FFT is compatible with the following FACPs:
• TR-2100ECSR / TR-2100ECSB
• TR-2100R / TR-2100B
• TR-R2100R/ TR-R2100B

Contact Us to Purchase
Features

• TR-FFT Fire Fighter Telephone module for control and annunciation of up to 72 remote telephone jacks
• Fire Fighter Phone Jack (TR-FPJ) provides a plug-in location for the TR-RHS
• Single telephone station mount comes in a lockable cabinet containing one remote handset. Available in Recessed mount (TR-STSR) or surface mount (TR-STSS).
• Fire Fighter Handset Cabinet (TR-HSC) is used to store ten fire fighter handsets (TR-RHS)
• System Status LEDs
• Supports two FFT-24 zone expanders
• The TR-FFT supports up to 72 TR-Minimon devices on one FFT system
• Simplified installation by using single loop design
• JumpStart® auto-programming
• For retrofit projects, TR-FFT is compatible with any UL listed 24V regulated power supply

Specifications

PHYSICAL
Flush Mount Dimensions: 20¼”W x 26¾”H x 2.5”- 3”D (51.4 W x 68 H x 6.4-7.6 D cm)
Overall Dimensions: 20”W x 26½”H x 4.6”D
(50.75 W x 67.3 H x 11.8 D cm)
Weight: 53 lbs.
Color: Red

 

ENVIRONMENTAL
Operating Temperature: 32°F to 120°F (0°C to 49°C) Humidity: 10 to 93% relative humidity
(noncondensing)

 

ELECTRICAL
Voltage for the TR-FFT must be a power-limited, filtered, non resettable nominal 24 VDC source. The voltage source must be within the range of 17-29 VDC.
Active Current: 230 mA
Standby Current: 120 mA
SLC Circuit: 32V; 150mA
Audio Circuits: 17V; 53mA

 

ORDERING INFORMATION
TR-FFT: Fire Fighters Telephone
TR-Minimon: Mini monitor module
TR-ISO: Fault Isolator Module

 

ECS ACCESSORIES
TR-24Z-EXT: 24 Zone Expander
TR-FPJ: Remote Phone Jack
TR-RHS: Fire Fighters Remote Hand Set
TR-HSC: Fire Fighters Handset Cabinet. Holds up to 10 remote handsets
TR-STSR: Single Telephone Station Recessed. A lockable cabinet containing one remote handset. TR-STSS: Single Telephone Station Surface Mount. A lockable cabinet containing one remote handset.

 

AGENCY LISTINGS AND APPROVALS
UL Listed

Contact Us

Subscribe to stay up to date on all the latest news

Click one of our representatives below to chat on WhatsApp.